Electrical Business

Features Code File Codes & Standards

Section 10: solidly grounded systems & bonding conductor size • Code File, July/August 2018

August 22, 2018 | By Tatjana Dinic


Figure 1

August 22, 2018 — In my last article about CE Code 2018’s Section 10 rewrite (EBMag May 2018), I explained some of the new structures and definitions, and touched upon the requirements and changes regarding grounding a consumer’s services at a meter-mounting device.

Here I will explain changes related to grounding a consumer’s service at the service box, and how to determine bonding conductor size.

“Single-point” grounding

Rule 10-210(d) requires there is no connection between the grounded conductor (neutral) and the non-current-carrying conductive parts of electrical equipment on the supply or load side of the grounding connections.

Advertisement

This represents a significant change to the current practice for services, where the meter is on the line side of the service box as permitted by Section 6 and the 2015 CE Code, which required no connection to the grounded conductor on the load side of the service.

This concept of “single-point” grounding past the supply authority demarcation point means the neutral bus in a meter mounting device is isolated from the meter enclosure, and that a bonding conductor is required between a meter mounting device and the service box. Figure 1 illustrates the concept of grounding at the consumer’s service.

You should be aware that standard meter mounting devices have a neutral bus connected to the enclosure so, to meet code requirements, a neutral bus shall be isolated from the enclosure and must be specifically requested, or the neutral conductor installed in a way that it is isolated from the meter enclosure.

Where the neutral bus is isolated from the meter enclosure, it is imperative you comply with Rule 10-210(d) requirements and provide a bonding conductor between a meter mounting device and the service box. Otherwise, supply authority workers could be exposed to a serious safety hazard. Were there a fault to ground in the service box, and no bonding conductor, there is no return path to a source for the fault current. Hence, the meter enclosure would remain energized.

One by-product of the changes in the 2018 code involves grounding two or more buildings supplied from the same service e.g. when school portables are added to the service. Based on the concept of single-point grounding (with the intent of eliminating objectionable current over grounding conductors), it is no longer permitted to connect the grounded conductor in each building to the grounding electrode and the non-current-carrying conductive parts of electrical equipment.

Instead, you must now employ a bonding conductor to connect the equipment bonding terminal in one building to the equipment bonding terminal in another, then run it with the feeder or branch circuit conductors, as in Figure 2.

Bonding conductor size

Finally, Rule 10-614 specifies the requirements for bonding conductor size. For installations as per Figure 1, the bonding conductor between a meter mounting device and the service box shall be determined in accordance with Table 16 based on the service conductors’ allowable ampacity (as there is no overcurrent device on the service box’s supply side).

For installations as per Figure 2, the bonding conductor between two buildings shall be determined in accordance with Table 16 based on the rating of the overcurrent device protecting ungrounded conductors.

This is also how one should size the system bonding jumper in both Figures 1 and 2. The change supports the objective of bonding, which is to facilitate the operation of protective devices.

To compensate for voltage drop, Rule 10-614 requires the bonding conductor’s size to increase when the circuit conductors’ size is increased.


Tatjana Dinic, P.Eng., is the acting director for Engineering & Program Development at Electrical Safety Authority (ESA) where, among other things, she is responsible for product safety, code development, improving harmonization and alternative compliance, and aging infrastructure programs. She is Professional Engineer with M. Eng. degree from University of Toronto and a member of CSA CE Code-Part I, Sections 4, 10 and 30. Tatjana can be reached at tatjana.dinic@electricalsafety.on.ca .

This article originally appeared in the July/August 2018 issue of Electrical Business Magazine.


Print this page

Advertisement

Stories continue below